Super Hot Allied Engineering Company - Manufacturer of Hydronic & Domestic Water Heating Equipment
 

Tankless Copper Coil Water Heater Series - Dimensions & Specifications

 
 
Literature
 

 
 Brochure 

 Dimensions & Specifications

Domestic Water Heating

Domestic Water Heating

Pool Heating

Pool Heating

Optional: The Bronze Circulator and Balancing Valve 2 may be omitted if the Pool Pump is correctly sized (i.e. the total Pool Pump head must include the Tankless Coil pressure drop.)

Cut out of a Copper Coil Water Heater       Tankless Coil Heat Transfer

MODEL NUMBER SERVICE WATER BOILER WATER
RECOVERY G.P.M
40 - 140°F
PRESSURE DROP
@ RATED FLOW
FT. OF WATER
FLOW G.P.M.
@ 200°F
PRESSURE DROP
@ RATED FLOW
FT. OF WATER
NET INPUT
M.B.H
C 2.5 2.5 13 13 5 125
C 5 5.0 12 26 5 249
C 10 10 15 51 5 498
C 15 15 13 77 5 747
C 20 20 12 103 5 996
C 25 25 13 129 5 1245
 
MODEL NUMBER WATER CONNECTIONS DIMENSIONS SHIPPING WEIGHT
LBS.
SERVICE BOILER HEIGHT DIAMETER
in mm in mm in mm in mm
C 2.5 1/2 13 1 1/4 32 13 3/4 349 7 1/2 sq 191 sq 26
C 5 3/4 19 2 51 15 381 16 1/4 413 65
C 10 1 25 2 51 20 508 16 1/4 413 90
C 15 1 1/4 32 3 76 25 635 16 1/4 413 115
C 20 1 1/2 38 3 76 30 762 16 1/4 413 145
C 25 1 1/2 38 3 76 35 889 16 1/4 413 165

NOTE: Ratings based on 100°F rise in service water (40-140°F) and 20°F drop in boiler water (200-180°F).
 

 